Technical data – Milton CAT D100-6S 100 kW Spec Sheet User Manual
Page 4
![background image](/manuals/268240/4/background.png)
STANDBY 100 ekW 100 kVA
PRIME 90 ekW 90 kVA
60 Hz 1800 rpm 240/120 Volts
TECHNICAL DATA
Open Generator Set – 1800 rpm/60 Hz/480 Volts
P3362A
Tier 3
STANDBY
PRIME
Generator Set Package Performance
Genset power rating @ 1.0 pf
Genset power rating with fan
100.0 kVA
100.0 ekW
90.0 kVA
90.0 ekW
Fuel Consumption
100% load with fan
75% load with fan
50% load with fan
23.1 L/hr
18.5 L/hr
13.8 L/hr
6.1 gal/hr
4.9 gal/hr
3.6 gal/hr
27.4 L/hr
21.9 L/hr
16.4 L/hr
7.9 gal/hr
6.3 gal/hr
4.6 gal/hr
Cooling System
1
Air flow restriction (system)
Engine coolant capacity with radiator/exp. tank
Engine coolant capacity
Radiator coolant capacity
0.12 kPa
17.0 L
7.0 L
10.0 L
0.48 in. water
4.5 Gal
1.8 Gal
2.6 Gal
0.12 kPa
17.0 L
7.0 L
10.0 L
0.48 in. water
4.5 Gal
1.8 Gal
2.6 Gal
Inlet Air
Combustion air inlet flow rate
8.5 m³/min
300.2 cfm
8.4 m³/min
296.6 cfm
Exhaust System
Exhaust stack gas temperature
Exhaust gas flow rate
Exhaust flange size (internal diameter)
Exhaust system back pressure (maximum)
506°C
20.0 m³/min
63.5 mm
15.0 kPa
943°F
706.3cfm
2.5 in
60.2 in. water
480°C
19.2 m³/min
63.5 mm
15.0 kPa
896°F
678.0 cfm
2.5 in
60.2 in. water
Heat Rejection
Heat rejection to coolant (total)
Heat rejection to exhaust (total)
Heat rejection to aftercooler
Heat rejection to atmosphere from engine
Heat rejection to atmosphere from generator
61.0 kW
87.0 kW
18.0 kW
18.0 kW
9.7 kW
3469 Btu/min
4948 Btu/min
1024 Btu/min
1023.6 Btu/min
551.6 Btu/min
57.0 kW
81.0 kW
17.0 kW
15.0 kW
8.4 kW
3242 Btu/min
4606 Btu/min
967 Btu/min
853 Btu/min
477.7Btu/min
Alternator
2
Motor starting capability @ 30% voltage dip
Frame
Rotor temperature rise
206 skV
LC3014B
130°C
234°F
206 skV
LC3014B
105°C
189°F
Lubrication System
Total oil capacity
Oil pan
8.0 L
7.0 L
2.1 gal
1.8 gal
8.0 L
7.0 L
2.1 gal
1.8 gal
1
For ambient and altitude capabilities consult your Cat dealer. Airflow restriction (system) is added to existing restriction from factory.
2
Generator temperature rise is based on a 40°C (104°F) ambient per NEMA MG1-32.
4