GENERATOR SET RATINGS
EMERGENCY STANDBY POWER (ESP)
OUTPUT AVAILABLE WITH VARYING LOAD FOR THE DURATION OF AN EMERGENCY
OUTAGE. AVERAGE POWER OUTPUT IS 70% OF THE ESP RATING. TYPICAL
OPERATION IS 50 HOURS PER YEAR, WITH MAXIMUM EXPECTED USAGE OF 200
HOURS PER YEAR.
STANDBY POWER RATING
OUTPUT AVAILABLE WITH VARYING LOAD FOR THE DURATION OF AN EMERGENCY
OUTAGE. AVERAGE POWER OUTPUT IS 70% OF THE STANDBY POWER RATING.
TYPICAL OPERATION IS 200 HOURS PER YEAR, WITH MAXIMUM EXPECTED USAGE
OF 500 HOURS PER YEAR.
PRIME POWER RATING
OUTPUT AVAILABLE WITH VARYING LOAD FOR AN UNLIMITED TIME. AVERAGE
POWER OUTPUT IS 70% OF THE PRIME POWER RATING. TYPICAL PEAK DEMAND IS
100% OF PRIME RATED EKW WITH 10% OVERLOAD CAPABILITY FOR EMERGENCY
USE FOR A MAXIMUM OF 1 HOUR IN 12. OVERLOAD OPERATION CANNOT EXCEED
25 HOURS PER YEAR.
CONTINUOUS POWER RATING
OUTPUT AVAILABLE WITH NON-VARYING LOAD FOR AN UNLIMITED TIME.
AVERAGE POWER OUTPUT IS 70-100% OF THE CONTINUOUS POWER RATING.
TYPICAL PEAK DEMAND IS 100% OF CONTINUOUS RATED EKW FOR 100% OF
OPERATING HOURS.