Enclosure operating characteristics – Milton CAT C15 Factory Weather Protected Enclosures User Manual
Page 2
![background image](/manuals/268196/2/background.png)
60 Hz (certified) WP
Ambient
Airflow
Sound Pressure Levels
Exhaust Back
Enclosure
Capability*
Rate
dBA @ Full Load
Pressure
ekW
kVA
PP/SB
°C
°F
m
3
/s
Cfm
1 m
7 m
15 m
in/H
2
O
kPa
550
687.5
SB
42
108
10.6
22,460
97.7
87.4
81.4
12.8
3.2
500
625.0
SB
46
115
10.6
22,460
97.2
86.9
80.9
12.2
3.1
455
568.8
PP
43
109
10.6
22,460
96.7
86.5
80.5
11.9
3.0
450
562.5
SB
49
120
10.6
22,460
96.7
86.5
80.5
11.9
3.0
410
512.5
PP
46
115
10.6
22,460
96.3
86.2
80.2
11.8
2.9
400
500.0
SB
52
126
10.6
22,460
96.2
86.1
80.1
11.7
2.9
365
456.3
PP
49
120
10.6
22,460
96.0
85.9
79.9
11.7
2.9
350
437.5
SB
55
131
10.6
22,460
95.8
85.8
79.8
11.6
2.9
320
400.0
PP
52
126
10.6
22,460
95.6
85.6
79.6
11.5
2.9
E N C L O S U R E S
*Ambient measured with Caterpillar Extended Life Coolant
ENCLOSURE OPERATING CHARACTERISTICS
Caterpillar is pleased to offer these additional generator set enclosure colors: white, bright beige,
and ASA 61 gray. (Caterpillar Yellow is standard color.)
4250 (167.32)
1800 (70.87)
1600 (62.99)
2515.2 (99.02)
Approximate weight of enclosure package without silencer: 4529 kg (9,984 lb)
Exact weight is dependant on options.
Information contained in this publication may be considered confidential.
www.cat-ElectricPower.com
Discretion is recommended when distributing.
Materials and specifications are subject to change without notice.
© 2006 Caterpillar
LEHE5492-01 (01-06)
CAT, CATERPILLAR, their respective logos and “Caterpillar Yellow,” as well as corporate and product
All Rights Reserved.
identity used herein, are trademarks of Caterpillar and may not be used without permission.
Printed in U.S.A.
Note: See “Fuel Tank Base” spec sheets for base dimensions.