Top only – Altronix AL175ULX Installation Instructions User Manual
Page 3
Terminal Identification:
Terminal
Function/Description
Legend
TRG1 & TRG2 These input terminals are designed to connect to the normally closed
outputs of an access control or fire alarm relay. These terminals control [LOCK+],
and [STRIKE+], as well as AL175ULX output relay contacts [N.C., N.O., C]
LOCK+
This terminal provides DC output voltage when [TRG1] and [TRG2] are shorted
together and are typically used to power Mag Locks.
STRIKE+
This terminal provides DC output voltage when [TRG1] and [TRG2] are unshorted
and are typically used to power Electric Strikes.
N.C., N.O., C
Isolated dry Form “C” contacts. Shorting [TRG1] and [TRG2] together causes these contacts to
switch. They are typically used for controlling multiple AL175ULXs with fire alarm tie-in
(Fig. 5 and Fig. 6, pg. 4)
.
AUX +
Continuous positive (+) DC power output voltage. It is not affected by TRG1, TRG2 operation.
COM -
Common negative (-) output (ground).
FACP
Spare wiring terminal used for fire alarm tie-in application (Fig. 4, pg. 4).
+ BAT --
Stand-by battery connections.
AC FAIL
Used to notify loss of AC e.g connect audible device or alarm panel relay normally energized
N.C., C, N.O.
When AC power is present. Contact rating 1 amp @ 28VDC.
Enclosure Dimensions:
13”H x 13.5”W x 3.25”D
0
0
0
.81"
0
1.1875"
1.1875"
3.25"
3.25"
0
1.1875"
3.25"
.75" 1.5"
6.25"
11"
1.4"
6.5"
5.5"
1.4"
11.66"
12.1"
13"
12.5"
11.75"
TOP ONLY
- 3 -