Led diagnostics, Terminal identification, Enclosure dimensions – Altronix AL400ULXJG Installation Instructions User Manual
Page 4

- 4 -
AL400ULXJ
Altronix is not responsible for any typographical errors.
Altronix Corp.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
web site: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.
IIAL400ULXJ
D11L
MEMBER
LED Diagnostics:
Red (DC)
Green (AC) Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC, Stand-by battery supplying power.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
Terminal Identification:
Terminal
Legend
Function/Description
L, G, N
Connect 115VAC 60 Hz. to these terminals: L to hot, N to Neutral, G to ground.
-- DC +
12VDC @ 4 amp or 24VDC @ 3 amp continuous power-limited output.
AC Fail
NC, NC, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized
when AC power is present. Contact rating 1 amp @ 28VDC.
Bat Fail
NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power
is present. Contact rating 1 amp @ 28VDC.
+ BAT --
Stand-by battery connections. Maximum charge current 0.7 amp.
Enclosure Dimensions
(H x W x D) (approximate)
:
18” x 14.5” x 4.625”
(457.2mm x 368.3mm x 117.48mm)
1.5”
(38.1mm)
1.0”
(25.4mm)
4.625”
(117.475mm)
1.0”
(25.4mm)
1.0”
(25.4mm)
1.25”
(31.75mm)
1.25”
(31.75mm)
1.0”
(25.4mm)
1.5”
(38.1mm)
1.5”
(38.1mm)
1.5”
(38.1mm)
1.5”
(38.1mm)
8.5”
(215.9mm)
18.0”
(457.2mm)
18.0”
(457.2mm)
18.0”
(457.2mm)
6.0”
(152.4mm)
2.5”
(63.5mm)
2.75”
(69.85mm)
2.75”
(69.85mm)
4.5”
(114.3mm)
4.5”
(114.3mm)
14.5”
(368.3mm)
14.5”
(368.3mm)
1.0”
(25.4mm)
1.0”
(25.4mm)
14.5”
(368.3mm)
2.5”
(63.5mm)
1.5”
(38.1mm)
2.5”
(63.5mm)