beautypg.com

Fig. 1, Board installation diagram, Fig. 2 - application diagram: led diagnostics – Altronix AL125ULX Installation Instructions User Manual

Page 3: Fig. 2a - sw1, Fig. 1a) nylon fastener, Springlock

background image

VR1

NO

NO

GND

GND

FA
C

P1
FA
C

P2

STRIKE+

COM

--

LOCK+

+ AUX

--

TRIG

INPUT

RESET

SW1

+ BAT --

XFMR

SW2:

12VDC - Open

24VDC - Closed

XFMR

115VAC

50/60 Hz,

.6 amp

Blue Lead

Yellow Lead

White

Lead

Black

Lead

Green

Lead

(ground)

STEP 1: Use these holes to mount

AL125ULB by pushing the nylon
circuit board fasteners (Fig. 1A)
through the back of the enclosure.
Nylon fasteners will snap into place.

(Fig. 1A)
Nylon Fastener

STEP 2: Mount AL125ULB circuit board to nylon

fasteners by pressing down circuit board onto
nylon fasteners.
Note: Springlock on fasteners is used to remove

AL125ULB circuit board.

Note: Four (4) nylon fasteners are

provided in the AL125ULB carton.

Springlock

Fig. 1

-

Board Installation Diagram:

Note:
- AL125UL, AL125ULX - Connect blue and yellow

leads of transformer to terminals marked [XFMR]
on the power supply board.

- AL125ULP, AL125ULE - Connect 24VAC @ 40VA

from UL Listed plug-in transformer to the terminals
marked [XFMR]on the power supply board.

VR1

NO

NO

GND

GND

FACP1 FACP2

STRIKE+

COM--

LOCK+

+ AUX --

TRIG INPUT

RESET

SW1

+

BA

T

--

XFMR

SW2:
12VDC - Open
24VDC - Closed

Normal Open

Access Control

Triggering

Device

Normal Open
Reset Device

2.2K EOL

(supplied)

MAG LOCK

NC

FACP

NO

FACP

{ }

Card

Reader

Fig. 2 - Application Diagram:

LED Diagnostics:

Red

Power Supply Status

ON

Normal function.

OFF

No DC output.

Slow Blink

Loss of AC.

Rapid Blink

Unit is triggered, awaiting reset. Fire alarm interface activated.

Fig. 2A - SW1

OPEN SWITCH

CLOSED SWITCH

ELECTRIC

STRIKE

STRIKE+ LOCK+

Com-

- 3 -