AL1012ULXseries

LED Diagnostics:
AL1012ULXB - Power Supply Board

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition

ON

OFF

Loss of AC, Stand-by battery supplying power

OFF

ON

No DC output

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

PD4/PD4CB/PD8/PD8CB - Power Distribution Module

Green

Power Distribution Module Status

ON

Normal operating condition.

Terminal Identification:
AL1012ULXB - Power Supply Board

Terminal Legend

Function/Description

L, G, N

Connect 115VAC to these terminals: L to Hot, N to Neutral, G to ground.

- DC +

12VDC @ 10 amp continuous non-power limited output.

AC FAIL

Indicates loss of AC power, e.g. connect to annuciator/alarm panel. Relay normally energized

NC, C, NO

when AC power is present. Contact rating 1 amp @ 30VDC. AC Fail condition will report
approximately one (1) to one minute after loss of AC. To delay report for 6 hours cut jumper
J1 on the Power Supply Board (AC trouble output delay option). If this mode is selected the Power
Supply Board must be reset by removing all power to it for 30 seconds.

BAT FAIL

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized

NO, C, NC

when DC power is present. Contact rating 1 amp @ 30VDC. Low battery conditions will report
approximately 10.5VDC Battery presence detection will report approimately 1 minute after battery
remains undetected (missing or removed).

- BAT +

Stand-by battery connections. Maximum charge rate .7 amp.

PD4/PD4CB/PD8/PD8CB - Power Distribution Module

Terminal Legend

Function/

PD4/PD4CB

PD8/PD8CB

Description

1P to 4P

1P to 8P

Positive DC power outputs.

1N to 4N

1N to 8N

Negative DC power outputs.