- 6 -

AL602ULADA

Terminal Identification Table:

AL600ADA Power Supply Board*

Terminal
Legend

Function/Description

L, G, N

Connect 120 VAC to these terminals: L to hot, N to neutral.

- DC +

24VDC @ 6.5 amp in alarm non-power limited output.

AC FAIL
NO, C, NC

Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation

devices, with AC present terminals marked NO and C are open, NC and C are closed.
When loss of AC occurs terminals marked NO and C are closed, NC and C are open.

AC LOCAL
NC, NO, C

Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation devices, with
AC present terminals marked NO and C are open, NC and C are closed. When loss of AC occurs termi-
nals marked NO and C are closed, NC and C are open.

BAT FAIL
NO, C, NC

Form “C” dry contacts used to signal low battery voltage or loss of battery voltage. Under normal
conditions terminals marked NO and C are open, NC and C are closed. During a trouble condition ter-
minals marked NO and C are closed, and NC and C are open (Fig. 2, pg. 7).

+ BAT -

Stand-by battery input (leads provided) (Fig. 2, pg. 7).

*Power Board Parameter Specifications:

• AC Fail condition will report approximately 30 seconds after loss of AC. To delay report for 2.5 to 3 hours cut

jumper AC DELAY on the Power Supply Board (AC trouble output delay option). If this mode is selected the Power

Supply Board must be reset by removing all power to it for 30 seconds.

• Low battery condition will report at approximately 21VDC.

• Battery presence detection will report with in 180 seconds after battery remains undetected (missing or removed).

A restored battery will report within 30 seconds.

LED Diagnostics:
AL600ADA - Power Supply Board

Red (DC)

Green (AC) Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC, Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

AL800LGK9E - Logic Board

LED

OFF

ON

BLINK (LONG)*

BLINK (SHORT)**

ON

Normal

Alarm Condition

Trouble Condition

Trouble Condition Memory

ON

Normal

Alarm Condition

Trouble Condition

Trouble Condition Memory

OFF

Normal

Alarm Condition

Trouble Condition

Trouble Condition Memory

OFF

Normal

Alarm Condition

Trouble Condition

Trouble Condition Memory

Input 1

Normal

Alarm Condition

Trouble Condition

---

Input 2

Normal

Alarm Condition

Trouble Condition

---

Fault

Normal

Alarm Condition

---

---