Battery size calculation worksheet.

A. AL1024ULX series internal current consumption

(standby)

_ _ _ _ _ _ _ _ _ _ _ _ .05 A

B. Load current consumption

(standby)

_ _ _ _ _ _ _ _ _ _ _ _ A

C. Standby time required (hours)

_ _ _ _ _ _ _ _ _ _ _ _ H

D. Battery capacity required for standby

(A+B)*C

_ _ _ _ _ _ _ _ _ _ _ _ AH

E. AL1024ULX series internal power consumption

(Alarm)

_ _ _ _ _ _ _ _ _ _ _ _ .05 A

F.

Load current consumption

(Alarm)

_ _ _ _ _ _ _ _ _ _ _ _ A

G. Alarm duration (Hours, 15 Min=.2 Hour)

(Alarm)

_ _ _ _ _ _ _ _ _ _ _ _ H

H. Battery capacity required for Alarm

(E+F)*G

_ _ _ _ _ _ _ _ _ _ _ _ AH

I.

Total calculated battery capacity

D+H

_ _ _ _ _ _ _ _ _ _ _ _ AH

J.

Battery capacity required

I*1.8 (safety factor) _ _ _ _ _ _ _ _ _ _ _ _ AH

Note: AL1024ULX series power supply is designed to work with batteries up to 65AH. Please note, line [I]
must not exceeds 36AH. You have to reduce either standby current consumption or standby time in order to
comply with requirement.

To determine actual battery size please round line [J] to the nearest larger standard battery size
(e.g. 3.5 AH = 4.0 AH).