Maintenance, Led diagnostics, Terminal identification – Altronix AL1024ULXB Installation Instructions User Manual
Page 2

Maintenance:
Unit should be tested at least once a year for the proper operation as
follows:
Output Voltage Test: Under normal load conditions, the DC output
voltage should be checked for proper voltage level.
Battery Test: Under normal load conditions check that the battery is
fully charged, check specified voltage both at battery terminal and at
the board terminals marked [+ BAT -] to insure there is no break in
the battery connection wires.
Note: Maximum charging current under discharge is 3.6 amp.
Note: Expected battery life is 5 years, however it is recommended
changing batteries in 4 years or less if needed.
LED Diagnostics:
Red (DC)
Green (AC)
Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC, Stand-by battery supplying power.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
Terminal Identification:
Terminal
Function/Description
Legend
L, G, N
Connect 115 VAC to these terminals:
L to hot, N to neutral, G to ground.
- DC +
24VDC @ 8 amp continuous, 10 amp in alarm non-power limited output.
AC FAIL
Used to notify loss of AC power, e.g.connect to audible device or alarm
N.O., C, N.C.
panel. Relay normally energized when AC power is present.
Contact rating 1 amp @ 28VDC.
AC or brownout fail is reported within 1 minute of event. To delay reporting of up to
6 hrs., cut “AC delay” jumper and reset power to unit.
BAT FAIL
Used to indicate low battery condition, e.g. connect to alarm panel.
N.O., C, N.C.
Relay normally energized when DC power is present.
Contact rating 1 amp @ 28VDC.
A removed battery is reported within 1 minute. Battery reconnection is reported
within 1 minute.
Low battery threshold: @ approximately 21VDC.
+ BAT -
Stand-by battery connections. Maximum charge current 3.6 amp.
Altronix Corp.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
web site: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.
IIAL1024ULXB Rev. 041602
K29D
MEMBER
-- DC +
BAT FAIL
NO C NC NO C NC
+ BAT ---
DC
AC FAIL
L G N
AC
Fuse
Cover
15A
250V
5A
250V
Fuse
Cover
Fig. 1