Altronix AL1024ULXB Installation Instructions User Manual
Al1024ulxb - ul recognized, power supply/charger
Agency Listings:
• UL Recognized component for Access Control
System Units (UL 294), Standard for Safety
for Fire Protective Signaling Systems (UL 1481).
Input:
• Input 115VAC / 60Hz, 4.4 amp.
Output:
• 24VDC output (UL 1481).
• 8 amp continuous supply current with 10 amp
supply current during alarm.
• 24VAC @ 10 amp (UL 294).
• Filtered and electronically regulated output.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 3.6 amp.
Battery Backup (continued):
• Automatic switch over to stand-by battery
when AC fails.
• Zero voltage drop when switched over to battery backup.
Visual Indicators:
• AC input and DC output LED indicators.
Supervision:
• AC fail supervision (form "C" contacts).
• Low battery and battery presence supervision
(form "C" contacts).
Additional Features:
• Short circuit and thermal overload protection.
Board Dimensions (approximate):
5.2”W x 7.7”L x 2.5”H
Stand-by Specifications:
Output
15 Min. of Stand-by & 4 hr. of Stand-by &
24 hr. of Stand-by & 60 hr. of Stand-by &
5 Mins. of Alarm
5 Mins. of Alarm
5 Mins. of Alarm
5 Mins. of Alarm
24VDC / 12AH Battery
Stand-by = 8 amp
Stand-by = 1.5 amp
Stand-by = 200mA
Stand-by = 100mA
Alarm = 10 amp
Alarm = 10 amp
Alarm = 10 amp
Alarm = 10 amp
24VDC / 65AH Battery
Stand-by = 8.0 amp
Stand-by = 1.5 amp
Stand-by = 500mA
Alarm = 10 amp
Alarm = 10 amp
Alarm = 10 amp
Installation Instructions:
The AL1024ULXB should be installed in accordance with article 760 of The National Electrical Code as well as
NFPA 72 and all applicable Local Codes.
1. Mount the AL1024ULXB in desired location/enclosure.
2. Connect unswitched AC power (115VAC 60Hz to terminals marked [L, G, N] (Fig. 1). Use 14 AWG or larger
for all power connections (Battery, AC input, DC output). Use 22 AWG to 18 AWG for power limited circuits
(AC Fail/Low Battery reporting). Keep power limited wiring separate from non-power limited wiring
(115VAC / 60Hz Input, Battery Wires). DC output Minimum .25” spacing must be provided.
3. Connect devices to be powered to terminals marked [-- DC +] (Fig. 1).
4. Measure output voltage before connecting devices. This helps avoid potential damage.
5. For Access Control applications, batteries are optional. When batteries are not used, a loss of AC will result in the
loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect
battery to terminals marked [+ BAT -] (Fig. 1).
6. It is required to connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1) supervisory
relay outputs. Use 22AWG to 18AWG wires. AC FAIL will report in 5 minutes.
To delay report 6 hours cut “AC delay” jumper.
AL1024ULXB - UL Recognized,
Power Supply/Charger
Rev. 041602
Overview:
The AL1024ULXB is a power supply that converts a 115VAC / 60Hz input, to a 24VDC non-power limited output,
(see specifications).
Specifications: