MOM5 Sub-Assembly

LED Diagnostic Table:

LED

ON

OFF

Power (Green)

Normal operation.

Loss of power to MOM5.

Trigger (Green) MOM5 triggered (alarm condition).

MOM5 in standby (non-alarm condition).

Outputs (Red)

Output tripped due to a short circuit or overload condition. Normal operation.

Terminal Identification:

Terminal Legend

Function/Description

– DC Input +

12VDC or 24VDC from power supply.

Trigger

This circuit is supervised by a 2.2 K EOL resistor. Initiating a short or open will cause
power to be dropped to all terminals marked Pos. (+) DC output (stand-by) and supply
power to all terminals marked Pos (+) DC output (alarm).

Input Neg (–),
Pos (+)

Applying voltage to terminals marked Neg (-) input Pos (+) FACP signaling output in
polarity shown will yield the same results as initiating trigger (mentioned above).

Neg (–) 1 thru 5

Supplies constant negative (-) voltage.

Pos (+) DC output (alarm)

Supplies positive (+) voltage when dry input or fire alarm (wet) trigger input.

Pos (+) DC output
(stand-by)

Supplies positive (+) voltage in normal condition. Power is removed when either input
trigger is activated.

NC, C, NO
Dry output

When the MOM5 is triggered terminals marked [C and NO] will close and the terminals
marked [C and NC] will open. This output is used to trip auxiliary devices. e.g. HVAC
Shutdown, Elevator Recall etc.

NC, C, NO
Power Fail

Form “C” contacts used for signaling when no voltage is present at – DC input +
terminals. Under normal conditions, terminals marked [NO and C] are open, [NC and C]
are closed. An occurance of trouble condition causes terminals marked [NO and C] to
close and terminals marked [NC and C] to open.

Fig. 1

Typical Application Diagrams:

TRIGGER

-- INPUT +

EOL 2.2K

(+)

(-)

DC VOLTAGE INPUT

FROM FACP SIGNALING

OUTPUT OR ACCESS

CONTROL DEVICE

NORMALLY CLOSED (NC)

INPUT FROM FACP

OR ACCESS CONTROL DEVICE

TRIGGER

-- INPUT +

EOL

2.2K

(+)

(-)

DC VOLTAGE INPUT

FROM FACP SIGNALING

OUTPUT OR ACCESS

CONTROL DEVICE

NORMALLY OPEN (NO)

INPUT FROM FACP

OR ACCESS CONTROL DEVICE

MOM5 module shown with wet and/or dry
normally closed trigger inputs

(Non-Latching):

MOM5 module shown with wet and/or dry normally open
trigger inputs

(Non-Latching):