beautypg.com

Terminal identification – Altronix OLS200 Installation Instructions User Manual

Page 2

background image

Terminal Identification:

Terminal Legend

Function/Description

L, G, N

Connect 115VAC to these terminals:
L to Hot, N to Neutral, G to ground.

– DC +

12VDC @ 10 amp continuous supply current.

AC FAIL
NC, C, NO

Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally
energized when AC power is present. Contact rating 1 amp @ 28VDC.

Low Battery
NC, C, NO

Used to indicate low battery condition, e.g. connect to alarm panel.
Relay normally energized when DC power is present.
Contact rating 1 amp @ 28VDC
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC.

– BAT +

Stand-by battery connections. Maximum charge rate 0.7 amp.

L

G

N

OFF ON

LOW BA

T

NC C NO NC C NO

AC

FA

IL

--- BAT +

--- DC +

AC DC

5A 250V

15A

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.
IIOLS200 - Rev. 010704

D25M

MEMBER