Altronix OLS200 Installation Instructions User Manual
Ols200 - off-line switching power supply/charger
Overview:
The OLS200 is a power supply/charger that converts 115VAC 50/60Hz input into a 12VDC @ 10 amp of continuous
supply current (see specifications).
Specifications:
Installation Instructions:
The OLS200 should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Mount the OLS200 in the desired location/enclosure.
2. Connect AC power to the terminals marked [L & N], connect ground to the terminal marked [G].
Use 18 AWG or larger for all power connections (Battery, DC output, AC input).
Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting).
Keep power-limited wiring separate from non power-limited wiring (DC output, 115VAC 50/60Hz Input,
Battery Wires). Minimum 0.25” spacing must be provided.
3. Measure output voltage before connecting devices. This helps avoiding potential damage.
4. Connect devices to be powered to the terminals marked [– DC + ].
5. When the use of stand-by batteries is desired, they must be lead acid or gel type.
6. Connect battery to the terminals marked [– BAT +] (battery leads included).
Note: When batteries are not used, a loss of AC will result in the loss of output voltage.
7. Connect appropriate signaling notification devices to AC Fail & Low battery supervisory
relay outputs marked [NC, C, NO].
LED Diagnostics:
Red (DC)
Green (AC) Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC, Stand-by battery supplying power.
OFF
ON
No DC output. Short circuit or thermal overload condition.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
OLS200 - Off-line Switching Power Supply/Charger
Input:
• 115VAC, 50/60Hz, 1.9 amp.
Output:
• 12VDC output.
• 10 amp continuous supply current.
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Automatic switch over to stand-by battery
when AC fails.
• Maximum charge current 0.7 amp.
Supervision:
• AC fail supervision (form “C” contacts).
• Low battery supervision (form “C” contacts).
Visual Indicators:
• AC input and DC output LED indicators.
Features:
• Power ON/OFF switch.
• Includes battery leads.
Board Dimensions (L x W x H approximate):
7.25” x 4.5” x 1.75” (184.1mm x 114.3mm x 44.45mm).