beautypg.com

Maintenance, Strikeit1 terminal identification, Request to exit pir jumpers – Altronix StrikeIt1 Installation Instructions User Manual

Page 5

background image

StrikeIt1

- 5 -

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

FACP Supervision: To insure proper connection and operation of the Fire Alarm disconnect hookup, remove wire from

the terminal marked [FACP] on StrikeIt1. With the [FA Select] jumper removed, locked Panic Hardware Devices will

unlock. With the [FA Select] jumper in place, unlocked Panic Hardware Devices will relock. When the wire is

reconnected to the [FACP] terminal the Panic Hardware Devices will relock with the [FA Select] jumper removed or will

unlock with the [FA Select] jumper in place.

Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage level.

Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at

battery terminal and at the board terminals marked [+ BAT -- ] to insure there is no break in the battery connection wires.

Note: Maximum charging current under discharge is 300mA.

Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.

Caution: For continuous protection against risk of electric shock and fire hazard, replace input fuse with the same type

and rating: 3.5 amp/250V. Do not expose to rain or moisture; indoor use only.

StrikeIt1 Terminal Identification:

Terminal Legend

Function/Description

+ 12VDC --

12VDC Auxiliary Output @ 1 amp.

-- 24VDC +

24VDC Auxiliary Output @ 1 amp.

+ BAT --

24VDC Stand-by Battery Connection (Two (2) 12VDC batteries wired in series).

-- OUT 1 +

Connect 24VDC Panic Hardware Device #1.

-- OUT 2 +

Connect 24VDC Panic Hardware Device #2.

FACP / GND

Normally Closed Dry Contact from Fire Alarm Control.

IN1 / GND

N/O Trigger input controls Output 1. May be held closed for extended unlocking.

IN2 / GND

N/O Trigger input controls Output 2. May be held closed for extended unlocking.

Delayed 1

Dry form “C” contacts provide a 1 second momentary pulse after a preset delay. With jumper
[DLY1] in place, the delay is 0.5 seconds. With jumper [DLY1] removed the delay is 1 second. This
permits the Panic Hardware Device to fully unlock before signaling auto operator to swing door.

Delayed 2

Dry form “C” contacts provide a 1 second momentary pulse after a preset delay. With jumper
[DLY2] in place, the delay is 0.5 seconds. With jumper [DLY2] removed the delay is 1 second.This
permits the Panic Hardware Device to fully unlock before signaling auto operator to swing door.

Follower 1

Dry form “C” contact. Energizes while output 1 is energized. Enables outside ADA switch plate
to actuate auto operator while door is unlocked. De-activates outside ADA actuator while door is
locked.

Follower 2

Dry form “C” contact. Energizes while output 2 is energized. Enables outside ADA switch plate
to actuate auto operator while door is unlocked. De-activates outside ADA actuator while door is
locked.

+ BAT --

-- 24VDC +

+ 12VDC --

XFMR

AC

FA

I

MIN

MAX

INP1

INP2

-- OUT1 + -- OUT2 +

DL

Y

1

DL

Y

2

IN1

GND

IN2

GND

GND

FACP

FA

SELECT

Panic Hardware Device

+

---

Fire

Alarm

Control

Panel

Automatic

Door

Operator

Automatic

Door

Operator

Rechargeable

Batteries

Request

to Exit

PIR

Panic Hardware Device

Auxiliary

Device

Auxiliary

24VDC

Device

Auxiliary

Device

12VDC

+

---

12VDC

FA

I

MIN

MAX

INP1

INP2

IN

1

GN

D

IN

2

GN

D

GN

DF

AC

P

Request

to Exit

PIR

Jumpers

Fig. 1a
Triggering Input 1 and Input 2
from a single actuating device.

Fig. 1