beautypg.com

Installation instructions, Fig. 1c – Altronix AL300ULXR Installation Instructions User Manual

Page 3

background image

AL300ULX series

- 3 -

Door

CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric

shock and fire hazard replace fuse with the same type and rating. Do not expose to rain or moisture.

Battery connection (non power limited)

Switch Position:
24VDC = SW1 OPEN
12VDC = SW1 CLOSED

Wire

Strap

(from

Enclosure

to Door)

Battery & AC

Supervision

Circuit

(power limited)

-

For 12VDC Operation

use hook-up in the

inset on the right

CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.

Keep power limited wiring separate from non-power limited. Use minimum 0.25" spacing.

12VDC Rechargeable Battery

(optional)

12VDC Rechargeable Battery

(optional)

115VAC

power mains

non power-

limited

Green

Lead

Class 1

+

DC ---

+

BAT ---

AC

DC

Ba
t

Risk of Fir

e,

Replace Fuse

s

As Marked

Opened - 24V

Closed - 12V

J1

SW1

Opened - 24V

Closed - 12V

SW1

5A 250

V

15A 250V

AC Delay

15

L

G

N

NC C NO NC C NO

AC Fail

Bat Fail

DC Output to devices

(power limited)

NC C NO NC C NO

Battery &

AC Supervision Circuit

(power limited)

J1

AC Delay

Fig. 1

Fig. 1a

Fig. 1b

Stand-by Specifications (total current shown):

Output

4 hr. of Stand-by &

5 Minutes of Alarm

24 hr. of Stand-by &

5 Minutes of Alarm

60 hr. of Stand-by &

5 Minutes of Alarm

12VDC / 40AH Battery

Stand-by = 2.5 amp

Alarm = 2.5 amp

Stand-by = 1.0 amp

Alarm = 2.5 amp

Stand-by = 300mA

Alarm = 2.5 amp

24VDC / 12AH Battery

--------

Stand-by = 200mA

Alarm = 2.5 amp

--------

24VDC / 40AH Battery

Stand-by = 2.5 amp

Alarm = 2.5 amp

Stand-by = 1.0 amp

Alarm = 2.5 amp

Stand-by = 300mA

Alarm = 2.5 amp

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 7, 8).
Secure enclosure to earth ground.

Fig. 1c