beautypg.com

Altronix AL600ULMR Installation Instructions User Manual

Page 4

background image

- 4 -

M series

Output Voltage and Stand-by Specification Charts:

AL300ULM

Output

Switch Position

4 hr. of Stand-by &

5 Minutes of Alarm

24 hr. of Stand-by &

5 Minutes of Alarm

60 hr. of Stand-by &

5 Minutes of Alarm

12VDC/40AH Battery

Closed

Stand-by = 2.5 amp

Alarm = 2.5 amp

Stand-by = 1.0 amp

Alarm = 2.5 amp

Stand-by = 300mA

Alarm = 2.5 amp

24VDC/12AH Battery

Open

-----------------------------------------

Stand-by = 200mA

Alarm = 2.5 amp

-----------------------------------------

24VDC/40AH Battery

Open

Stand-by = 2.5 amp

Alarm = 2.5 amp

Stand-by = 1.0 amp

Alarm = 2.5 amp

Stand-by = 300mA

Alarm = 2.5 amp

AL400ULM

Output

Switch Position

4 hr. of Stand-by &

5 Minutes of Alarm

24 hr. of Stand-by &

5 Minutes of Alarm

60 hr. of Stand-by &

5 Minutes of Alarm

12VDC/40AH Battery

Closed

Stand-by = 4.0 amp

Alarm = 4.0 amp

Stand-by = 1.0 amp

Alarm = 4.0 amp

Stand-by = 300mA

Alarm = 4.0 amp

24VDC/12AH Battery

Open

-----------------------------------------

Stand-by = 200mA

Alarm = 3.0 amp

-----------------------------------------

24VDC/40AH Battery

Open

Stand-by = 3.0 amp

Alarm = 3.0 amp

Stand-by = 1.0 amp

Alarm = 3.0 amp

Stand-by = 300mA

Alarm = 3.0 amp

AL600ULM

Output

Switch Position

4 hr. of Stand-by &

5 Minutes of Alarm

24 hr. of Stand-by &

5 Minutes of Alarm

60 hr. of Stand-by &

5 Minutes of Alarm

12VDC/40AH Battery

Closed

Stand-by = 6.0 amp

Alarm = 6.0 amp

Stand-by = 1.0 amp

Alarm = 6.0 amp

Stand-by = 300mA

Alarm = 6.0 amp

24VDC/12AH Battery

Open

-----------------------------------------

Stand-by = 200mA

Alarm = 3.0 amp

-----------------------------------------

24VDC/40AH Battery

Open

Stand-by = 6.0 amp

Alarm = 6.0 amp

Stand-by = 1.0 amp

Alarm = 6.0 amp

Stand-by = 300mA

Alarm = 6.0 amp

AL1012ULM

Output
12VDC/12AH Battery

15 Minutes of Stand-by @ 10 amp

AL1024ULM

Output

15 mins of Stand-by &

5 Minutes of Alarm

4 hr. of Stand-by &
5 Minutes of Alarm

24 hr. of Stand-by &

5 Minutes of Alarm

60 hr. of Stand-by &

5 Minutes of Alarm

24VDC/12AH
Battery

Stand-by = 7.7 amp

Alarm = 9.7 amp

Stand-by = 1.2 amp

Alarm = 9.7 amp

-----------------------------------------

-----------------------------------------

24VDC/65AH
Battery

-----------------------------------------

Stand-by = 7.7 amp

Alarm = 9.7 amp

Stand-by = 1.2 amp

Alarm = 9.7 amp

Stand-by = 200mA

Alarm = 9.7 amp