M series
Output Voltage and Stand-by Specification Charts:
AL300ULM
Output
Switch Position
4 hr. of Stand-by &
5 Minutes of Alarm
24 hr. of Stand-by &
5 Minutes of Alarm
60 hr. of Stand-by &
5 Minutes of Alarm
12VDC/40AH Battery
Closed
Stand-by = 2.5 amp
Alarm = 2.5 amp
Stand-by = 1.0 amp
Alarm = 2.5 amp
Stand-by = 300mA
Alarm = 2.5 amp
24VDC/12AH Battery
Open
-----------------------------------------
Stand-by = 200mA
Alarm = 2.5 amp
-----------------------------------------
24VDC/40AH Battery
Open
Stand-by = 2.5 amp
Alarm = 2.5 amp
Stand-by = 1.0 amp
Alarm = 2.5 amp
Stand-by = 300mA
Alarm = 2.5 amp
AL400ULM
Output
Switch Position
4 hr. of Stand-by &
5 Minutes of Alarm
24 hr. of Stand-by &
5 Minutes of Alarm
60 hr. of Stand-by &
5 Minutes of Alarm
12VDC/40AH Battery
Closed
Stand-by = 4.0 amp
Alarm = 4.0 amp
Stand-by = 1.0 amp
Alarm = 4.0 amp
Stand-by = 300mA
Alarm = 4.0 amp
24VDC/12AH Battery
Open
-----------------------------------------
Stand-by = 200mA
Alarm = 3.0 amp
-----------------------------------------
24VDC/40AH Battery
Open
Stand-by = 3.0 amp
Alarm = 3.0 amp
Stand-by = 1.0 amp
Alarm = 3.0 amp
Stand-by = 300mA
Alarm = 3.0 amp
AL600ULM
Output
Switch Position
4 hr. of Stand-by &
5 Minutes of Alarm
24 hr. of Stand-by &
5 Minutes of Alarm
60 hr. of Stand-by &
5 Minutes of Alarm
12VDC/40AH Battery
Closed
Stand-by = 6.0 amp
Alarm = 6.0 amp
Stand-by = 1.0 amp
Alarm = 6.0 amp
Stand-by = 300mA
Alarm = 6.0 amp
24VDC/12AH Battery
Open
-----------------------------------------
Stand-by = 200mA
Alarm = 3.0 amp
-----------------------------------------
24VDC/40AH Battery
Open
Stand-by = 6.0 amp
Alarm = 6.0 amp
Stand-by = 1.0 amp
Alarm = 6.0 amp
Stand-by = 300mA
Alarm = 6.0 amp
AL1012ULM
Output
12VDC/12AH Battery
15 Minutes of Stand-by @ 10 amp
AL1024ULM
Output
15 mins of Stand-by &
5 Minutes of Alarm
4 hr. of Stand-by &
5 Minutes of Alarm
24 hr. of Stand-by &
5 Minutes of Alarm
60 hr. of Stand-by &
5 Minutes of Alarm
24VDC/12AH
Battery
Stand-by = 7.7 amp
Alarm = 9.7 amp
Stand-by = 1.2 amp
Alarm = 9.7 amp
-----------------------------------------
-----------------------------------------
24VDC/65AH
Battery
-----------------------------------------
Stand-by = 7.7 amp
Alarm = 9.7 amp
Stand-by = 1.2 amp
Alarm = 9.7 amp
Stand-by = 200mA
Alarm = 9.7 amp