- 2 -

M series

Overview:

These multi-output access control power supply/chargers are specifically designed for use with access control systems and

accessories. These units convert a 115VAC, 60Hz input into five (5) individually protected 12VDC or 24VDC outputs (see

specifications). Each output will route power to a variety of access control hardware devices including Mag Locks, Electric

Strikes, Magnetic Door Holders, etc. These outputs will operate in both Fail-Safe and Fail-Secure modes. Controlled

trigger input is achieved through normally open [NO] or normally closed [NC] supervised input or the polarity reversal

from an FACP (Fire Alarm Control Panel). A form “C” dry output relay enables HVAC Shutdown, Elevator Recall or may

be used to trigger auxiliary devices.

M Series Power Supply Configuration Reference Chart:

Altronix
Model
Number

12VDC Total Output Current

(amp)

24VDC Total Output Current

(amp)

Outputs

Class 2 Rated Power Limited

115VAC 60Hz Input (current draw/amp)

Individual Output Rating (amp)

Power Supply Board Input Fuse Rating

Power Supply Board Output Fuse Rating

Agency Listings

UL Listings and

File Numbers

AL300ULM

2.5

2.5

5 Yes 3.5 amp

2

5A/

250V

15A/

32V

UL 294

UL Listed Access Control System Unit.

UL 603

UL Listed for Burglar Alarms Systems.

UL 1069

UL Listed Hospital Signaling and

Nurse Call Equipment.

UL 1481

UL Listed for Power Supplies for

Fire Protective Signaling Systems

AL400ULM

4

3

5 Yes 3.5 amp

2

5A/

250V

15A/

32V

AL600ULM

6

6

5 Yes 3.5 amp

2

5A/

250V -------------

AL1012ULM

10

------------ 5 Yes 2.6 amp

2

5A/

250V

15A/

32V

UL File # BP617

UL 294

UL Listed Access Control System Unit.

AL1024ULM ------------

10

5 Yes 4.2 amp

2

5A/

250V

15A/

32V

UL 294

UL Listed Access Control System Unit.

UL 1481

UL Listed for Power Supplies for

Fire Protective Signaling Systems

Specifications:

Input:

• Power input 115VAC 60Hz (see reference chart above).

• Fire Alarm Panel or Access Control System trigger

inputs. [NO] or [NC] supervised trigger input and

polarity reversal trigger input (4mA draw from FACP).

Output:

• Five (5) individual power limited class 2 outputs.

• Current limit is 2 amp @ 12VDC or 24VDC

per output (12VDC only for AL1012ULM,

24VDC only for AL1024ULM).

Burglar Alarm Applications (UL 603)

AL300ULM and AL400ULM only:

12VDC = 10VDC-13.2VDC.

24VDC = 20VDC-26.4VDC.

• Filtered and electronically regulated outputs.

• Thermal and short circuit protection with auto reset.

• Overload protection.

• Output relay energizes when unit is triggered

(form “C” contact rated 1 amp @ 28VDC).

Battery Backup:

• Built-in charger for sealed lead acid or gel type batteries.

• Automatic switch over to stand-by battery when AC fails.

Battery Backup (cont’d):

• Zero voltage drop when switching over to

battery backup.

• AL300ULM, AL400ULM, AL600ULM and

AL1012ULM (Power Supply Board) maximum

charge current 0.7 amp.

AL1024ULM (Power Supply Board) maximum

charge current 3.6 amp.

• AL300ULM, AL400ULM and AL600ULM enclosures

accommodate up to two (2) 12VDC/7AH batteries.

• AL1012ULM should be fitted with

one (1) 12VDC/12AH battery.

• AL1024ULM should be fitted with

two (2) 12VDC/12AH batteries.

Visual Indicators:

• DC output LED indicator.

• LEDs indicate condition of power outputs.

• Power & input trigger LED’s.

Supervision:

• AC fail supervision (form “C” contact).

• Low battery supervision (form “C” contact).

• Battery presence supervision (form “C” contact).