beautypg.com

Altronix Maximal7 Installation Instructions User Manual

Page 7

background image

Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused)

- 7 -

Fig. 1

Maximal3
Power Supply Board

Power Supply Board Stand-by Battery Specifications:

Altronix

Model:

Power Supply Board

Battery

20 Min. of

Backup

4 hr. of

Backup

24 hr. of

Backup

Maximal3

AL600ULXB

(Refer to Fig. 1a, pg. 7 for Switch

[SW1] location and position)

12VDC/40AH*

N/A

5.0 amp

N/A

24VDC/40AH*

N/A

5.4 amp

0.7 amp

Maximal5

AL1012ULXB

(Factory set at 12VDC)

12VDC/12AH

9.0 amp

Battery capacity for

emergency stand-by

at least 20 min.

N/A

Maximal7

AL1024ULXB2

(Factory set at 24VDC)

24VDC/12AH

7.7 amp

1.2 amp

200mA

24VDC/65AH*

N/A

7.7 amp

1.2 amp

*Note: Additional battery enclosure required (Figs. 5-7, pgs. 11-13).

Power Supply Board Output Voltage Settings:

+ DC -

--

OPEN - 24V CLOSED - 12V

OPEN SWITCH

CLOSED SWITCH

Switch Detail

Fig. 1a