beautypg.com

Altronix Maximal7 Installation Instructions User Manual

Page 11

background image

Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused)

- 11 -

NEC Power-Limited Wiring Requirements for Maximal3:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring
must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring
and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this
is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may
be used. For power- limited applications, use of conduit is optional. All field wiring connections must be made employing
suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire, (Fig, 5a).

Fig. 5

External

Jacketed

Shield

Incorrect Wire

Handling

Correct Wire

Handling

Pull back

external jacketed

shield approx. 1/2”.

Wire

Insulation

Solid Copper

Conductors

Fig. 5a

115VAC Input

60Hz

(non power-limited)

Optional Battery

Enclosure

(non power-limited)

Supervisory

Connections

(power-limited)

Battery

Connections

(non power-limited)

ACM8

outputs

(non power-

limited)