beautypg.com

Power supply/chargers operating guide – Altronix eFlow102NX16D Installation Instructions User Manual

Page 16

background image

CUT ALONG DOTTED LINE

Power Supply/Chargers Operating Guide

Models Include:

Model

Input

120VAC, 60Hz

Output

Auxiliary

Power-Limited

Output (unswitched)

Ripple

Voltage

12VDC

24VDC

eFlow102N,
eFlow102N8, eFlow102N8D,
eFlow102N16, eFlow102N16D

3.5 amp

10 amp

----------

1 amp

760mV

eFlow102NX,
eFlow102NX8, eFlow102NX8D,
eFlow102NX16, eFlow102NX16D

Overview:

The eFlow102N series power supply/chargers convert a 120VAC, 60Hz input, to a 12VDC output.

Stand-by Specifications:

Battery

Burg. Applications

4 hr. Stand-by/

15 min. Alarm

Fire Applications

24 hr. Stand-by/

5 min. Alarm

Access Control

Applications

Stand-by

7AH

0.4 amp/10 amp

N/A

5 Mins./10 amp

12AH

1 amp/10 amp

0.3 amp/10 amp

15 Mins./10 amp

40AH

6 amp/10 amp

1.2 amp/10 amp

Over 2 Hours/10 amp

65AH

6 amp/10 amp

1.5 amp/10 amp

Over 4 Hours/10 amp

Battery Backup:

• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 1.54 amp.
• Automatic switch over to stand-by battery when AC fails. Transfer to stand-by battery power is instantaneous
with no interruption.

LED Diagnostics:

Red (DC)

Green (AC/AC1) Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC, Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Installing Company: _________________________________ Service Rep. Name: ___________________________________________________

Address: _______________________________________________________________________ Phone #: _______________________________

Refer to the eFlow Power Supply/Chargers Installation Guide: IIeFlow102N Series, Rev. 102NRP052213 for complete
instructions. This sheet is to be removed, framed and posted next to the unit.