Power supply/chargers operating guide – Altronix eFlow102NX16D Installation Instructions User Manual
Page 16

CUT ALONG DOTTED LINE
Power Supply/Chargers Operating Guide
Models Include:
Model
Input
120VAC, 60Hz
Output
Auxiliary
Power-Limited
Output (unswitched)
Ripple
Voltage
12VDC
24VDC
eFlow102N,
eFlow102N8, eFlow102N8D,
eFlow102N16, eFlow102N16D
3.5 amp
10 amp
----------
1 amp
760mV
eFlow102NX,
eFlow102NX8, eFlow102NX8D,
eFlow102NX16, eFlow102NX16D
Overview:
The eFlow102N series power supply/chargers convert a 120VAC, 60Hz input, to a 12VDC output.
Stand-by Specifications:
Battery
Burg. Applications
4 hr. Stand-by/
15 min. Alarm
Fire Applications
24 hr. Stand-by/
5 min. Alarm
Access Control
Applications
Stand-by
7AH
0.4 amp/10 amp
N/A
5 Mins./10 amp
12AH
1 amp/10 amp
0.3 amp/10 amp
15 Mins./10 amp
40AH
6 amp/10 amp
1.2 amp/10 amp
Over 2 Hours/10 amp
65AH
6 amp/10 amp
1.5 amp/10 amp
Over 4 Hours/10 amp
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 1.54 amp.
• Automatic switch over to stand-by battery when AC fails. Transfer to stand-by battery power is instantaneous
with no interruption.
LED Diagnostics:
Red (DC)
Green (AC/AC1) Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC, Stand-by battery supplying power.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
Installing Company: _________________________________ Service Rep. Name: ___________________________________________________
Address: _______________________________________________________________________ Phone #: _______________________________
Refer to the eFlow Power Supply/Chargers Installation Guide: IIeFlow102N Series, Rev. 102NRP052213 for complete
instructions. This sheet is to be removed, framed and posted next to the unit.
Rev. 102NRP052213