3 dimensions – VEGA VEGABAR 82 Profibus PA - Operating Instructions User Manual
Page 74
74
11 Supplement
VEGABAR 82 • Profibus PA
45031-EN-131107
Status code
Description according to
Profibus standard
Possible cause
0 x 04
bad - configuration error
– Adjustment error
– Configuration error with PV-Scale (PV-Span too
small)
– Unit irregularity
– Error in the linearization table
0 x 0C
bad - sensor failure
– Hardware error
– Converter error
– Leakage pulse error
– Trigger error
0 x 10
bad - sensor failure
– Measured value generation error
– Temperature measurement error
0 x 1f
bad - out of service con-
stant
"Out of Service" mode switched on
0 x 44
uncertain - last unstable
value
Failsafe replacement value (Failsafe-Mode = "Last val-
ue" and already valid measured value since switching
on)
0 x 48
uncertain substitute set
– Switch on simulation
– Failsafe replacement value (Failsafe-Mode = "Fsafe
value")
0 x 4c
uncertain - initial value
Failsafe replacement value (Failsafe-Mode = "Last valid
value" and no valid measured value since switching on)
0 x 51
uncertain - sensor; con-
version not accurate - low
limited
Sensor value < lower limit
0 x 52
uncertain - sensor; con-
version not accurate - high
limited
Sensor value > upper limit
0 x 80
good (non-cascade) - OK OK
0 x 84
good (non-cascade) - ac-
tive block alarm
Static revision (FB, TB) changed (10 sec. active, after
the parameter of the static category has been written)
0 x 89
good (non-cascade) - ac-
tive advisory alarm - low
limited
Lo-Alarm
0 x 8a
good (non-cascade) - ac-
tive advisory alarm - high
limited
Hi-Alarm
0 x 8d
good (non-cascade) - ac-
tive critical alarm - low
limited
Lo-Lo-Alarm
0 x 8e
good (non-cascade) - ac-
tive critical alarm - high
limited
Hi-Hi-Alarm
11.3 Dimensions
The following dimensional drawings represent only an extract of the possible versions. Detailed
dimensional drawings can be downloaded at