VEGA VEGABAR 82 Profibus PA - Operating Instructions User Manual
Page 45

45
6 Set up with the display and adjustment module
VEGABAR 82 • Profibus PA
45031-EN-131107
grammable linearization curve as well as the measured value memory
will be deleted.
Basic settings: Resetting the parameter settings incl. special
parameters to the default values of the respective instrument. A pro-
grammed linearization curve as well as the measured value memory
is deleted.
The following table shows the default values of the instrument. De-
pending on the instrument version or application, all menu items may
not be available or some may be differently assigned:
Reset - Setup
Menu item
Parameter
Default value
Sensor address
126
Measurement
loop name
Sensor
Application
Application pro-
cess pressure
Application level
No reset
Slave for elec-
tronic differential
pressure
No reset
Units
Unit of measure-
ment
mbar (with nominal measuring range
≤400 mbar)
bar (with nominal measuring rang-
es ≥1 bar)
Temperature unit °C
Position correc-
tion
0.00 bar
Adjustment
Zero/Min. adjust-
ment
0.00 bar
0.00 %
Span/Max. adjust-
ment
Nominal measuring range in bar
100.00 %
Damping
Integration time
0.0 s
Linearization
Linear
AI FB 1
Channel
Primary Value
Scaling format
Pressure
Scaling
0 % corresponds to 0 bar
100 % corresponds to measuring
range final value
Damping
PV FTime 0 s
Lock adjustment
Released