11 Supplement

VEGABAR 82 • Profibus PA

45031-EN-131107

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

0 … 5 psi

435 psi

0 psi

0 … 15 psi

510 psi

0 psi

0 … 30 psi

725 psi

0 psi

0 … 150 psi

1300 psi

0 psi

0 … 300 psi

1900 psi

0 psi

0 … 900 psi

2900 psi

0 psi

0 … +1450 psig
(only for measuring cell ø 28 mm)

2900 psig

0 psi

Output variable
Output signal

digital output signal, format according to IEEE-754

Sensor address

126 (default setting)

Damping (63 % of the input variable)

0 … 999 s, adjustable

Profibus PA profile

3.02

Number of FBs with AI (function blocks

with analogue input)

3

Default values

Ʋ 1. FB

PV

Ʋ 2. FB

SV 1

Ʋ 3. FB

SV 2

Current value

Ʋ Non-Ex and Ex ia instrument

10 mA, ±0.5 mA

Ʋ Ex-d instruments

16 mA, ±0.5 mA

Resolution, digital

< 1 mm (0.039 in)

Dynamic behaviour output
Run-up time approx.

10 s

Dynamic characteristics, depending on medium, temperature and, if applicable, chemical seal