6 Set up with the display and adjustment module
VEGABAR 82 • Profibus PA
45031-EN-131107
4. Units
In this menu item you determine the adjustment and temperature
units of the instrument. Depending on the selected application in the
menu item "Application", different adjustment units are available.
5. Position correction
In this menu item you compensate the influence of the installation
position of the instrument (offset) to the measured value.
6. zero adjustment
In this menu item you carry out the zero adjustment for the processs
pressure.
Enter the respective pressure value for 0 %.
7. span adjustment
In this menu item you carry out the span adjustment for the processs
pressure
Enter the respective pressure value for 100 %.
5. Position correction
In this menu item you compensate the influence of the installation
position of the instrument (offset) to the measured value.
6. Max. adjustment
In this menu item you carry out the max. adjustment for level
Enter the percentage value and the corresponding value for the max.
level.
7. Min. adjustment
In this menu item you carry out the min. adjustment for level
Enter the percentage value and the corresponding value for the min.
level.
8. AI FB1 Channel
In this menu item you can select the function of the first Function
Block. AI stands for Analog Input.
With this you can adjust the value for the Primary Value (PV). Further
settings (SV, TV) must be carried out via PACTware.
Quick setup - Process
pressure measurement
Quick setup - Level meas-
urement
Quick setup - Function
Block