Nominal range
Overload capacity, max.
pressure
Overload capacity, min. pres-
sure
0 … 0.1 bar/0 … 10 kPa
15 bar/1500 kPa
0.8 bar abs.
0 … 1 bar/0 … 100 kPa
35 bar/3500 kPa
0 bar abs.
0 … 2.5 bar/0 … 250 kPa
50 bar/5000 kPa
0 bar abs.
0 … 10 bar/0 … 1000 kPa
90 bar/9000 kPa
0 bar abs.
0 … 25 bar/0 … 2500 kPa
130 bar/13000 kPa
0 bar abs.
0 … 60 bar/0 … 6000 kPa
200 bar/20000 kPa
0 bar abs.
0 … +100 bar/0 … +10000 kPa
(only for measuring cell ø 28 mm)
200 bar/20000 kPa
0 bar abs.
Nominal measuring ranges and overload capacity in psi
The specifications are only an overview and refer to the measuring cell. Limitations due to the
material and version of the process fitting as well as the selected pressure type are possible. The
specifications on the nameplate apply.
Nominal range
Overload capacity, max.
pressure
Overload capacity, min. pres-
sure
Gauge pressure
0 … +0.4 psig
(only for measuring cell ø 28 mm)
+75 psig
-0.725 psig
0 … +1.5 psig
+225 psig
-2.901 psig
0 … +5 psig
+435 psig
-11.60 psig
0 … +15 psig
+510 psig
-14.51 psig
0 … +30 psig
+725 psig
-14.51 psig
0 … +150 psig
+1300 psig
-14.51 psig
0 … +300 psig
+1900 psig
-14.51 psig
0 … +900 psig
+2900 psig
-14.51 psig
0 … +1500 psig
(only for measuring cell ø 28 mm)
+2900 psig
-14.51 psig
-14.5 … 0 psig
+510 psig
-14.51 psig
-14.5 … +20 psig
+580 psig
-14.51 psig
-14.5 … +150 psig
+1300 psig
-14.51 psig
-14.5 … +300 psig
+1900 psig
-14.51 psig
-14.5 … +900 psig
+2900 psig
-14.51 psig
-14.5 … +1500 psig
(only for measuring cell ø 28 mm)
+2900 psig
-14.51 psig
-0.7 … +0.7 psig
+225 psig
-2.901 psig
-3 … +3 psig
+290 psi
-5.800 psig
-7 … +7 psig
+510 psig
-14.51 psig
Absolute pressure
0 … 1.5 psi
225 psig
0 psi