VEGA VEGABAR 81 4 … 20 mA_HART - Operating Instructions User Manual
Page 44
44
6 Set up with the display and adjustment module
VEGABAR 81 • 4 … 20 mA/HART
45018-EN-131010
The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of
shipment from the factory incl. the order-specific settings. A user-pro-
grammable linearization curve as well as the measured value memory
will be deleted.
Basic settings: Resetting the parameter settings incl. special
parameters to the default values of the respective instrument. A pro-
grammed linearization curve as well as the measured value memory
is deleted.
The following table shows the default values of the instrument. De-
pending on the instrument version or application, all menu items may
not be available or some may be differently assigned:
Reset - Setup
Menu item
Parameter
Default value
Measurement
loop name
Sensor
Application
Application pro-
cess pressure
Application level
No reset
Slave for elec-
tronic differential
pressure
No reset
Units
Unit of measure-
ment
mbar (with nominal measuring range
≤400 mbar)
bar (with nominal measuring rang-
es ≥1 bar)
Temperature unit °C
Position correc-
tion
0.00 bar
Adjustment
Zero/Min. adjust-
ment
0.00 bar
0.00 %
Span/Max. adjust-
ment
Nominal measuring range in bar
100.00 %
Damping
Integration time
0.0 s
Current output
Current output -
Mode
Output characteristics
4 … 20 mA
Reaction when malfunction occurs
≤ 3.6 mA
Current output -
Min./Max.
3.8 mA
20.5 mA