6 Set up with the display and adjustment module
VEGABAR 81 • 4 … 20 mA/HART
45018-EN-131010
4. Position correction
In this menu item you compensate the influence of the installation
position of the instrument (offset) to the measured value.
5. zero adjustment
In this menu item you carry out the zero adjustment for the processs
pressure.
Enter the respective pressure value for 0 %.
6. span adjustment
In this menu item you carry out the span adjustment for the processs
pressure
Enter the respective pressure value for 100 %.
4. Position correction
In this menu item you compensate the influence of the installation
position of the instrument (offset) to the measured value.
5. Max. adjustment
In this menu item you carry out the max. adjustment for level
Enter the percentage value and the corresponding value for the max.
level.
6. Min. adjustment
In this menu item you carry out the min. adjustment for level
Enter the percentage value and the corresponding value for the min.
level.
The quick setup is hence finished.
6.4 Parameter adjustment - Extended adjustment
For technically demanding measurement loops you can carry out
extended settings in "Extended adjustment".
The main menu is divided into five sections with the following func-
tions:
Adjustment - Process
pressure measurement
Adjustment - Level meas-
urement
Main menu
Main menu