6 Set up with the display and adjustment module

VEGABAR 81 • 4 … 20 mA/HART

45018-EN-131010

– Save value

[->] key:

– Presentation, change measured value

– Select list entry

– Select editing position

[+] key:

– Change value of the parameter

[ESC] key:

– Interrupt input

– Jump to next higher menu

The sensor is adjusted via the four keys of the display and adjust-

ment module. The LC display indicates the individual menu items. The

functions of the individual keys are shown in the above illustration.

Approx. 60 minutes after the last pressing of a key, an automatic reset

to measured value indication is triggered. Any values not confirmed

with [OK] will not be saved.

6.3 Parameter adjustment - Quick setup

To quickly and easily adapt the sensor to the application, select

the menu item "Quick setup" in the start graphic on the display and

adjustment module.

Carry out the following steps in the below sequence.
You can find "Extended adjustment" in the next sub-chapter.
1. Measurement loop name

In the first menu item you assign a suitable measurement loop name.

Permitted are names with max. 19 characters.
2. Application

In this menu item you activate/deactivate the slave for the electronic

differential pressure and select the application. With process pressure

transmitters, the selection comprises process pressure and level

measurement; with suspension pressure transmitters it comprises

level measurement.
3. Units

In this menu item you determine the adjustment and temperature

units of the instrument. Depending on the selected application in the

menu item "Application", different adjustment units are available.

Adjustment system

Presettings