VEGA VEGAFLEX 82 4 … 20 mA_HART four-wire User Manual
Page 41
41
6 Set up with the display and adjustment module
VEGAFLEX 82 • 4 … 20 mA/HART - four-wire
41830-EN-130314
Menu
Menu item
Default value
Setup
Block operation
Released
Measurement
loop name
Sensor
Units
Distance unit: mm
Temperature unit: °C
Probe length
Length of the probe Ex factory
Product type
Bulk solid
Application
Level, vessel
Medium, dielectric
constant
Granules, powder, 1.5 … 3
Max. adjustment
0.000 m(d) - note blocking distances
Min. adjustment
Probe length - take dead band into
account
Linearization
Linear
Damping
0.0 s
Scaling size
Volume in l
Current output,
adjustment
0.00 lin %, 0 l
100.00 lin %, 100 l
Current output
mode
Last measured value
Current output
Min./Max.
Min. current 3.8 mA, max. current
20.5 mA
Display
Language
As set in the device
Displayed value 1 Filling height Level
Displayed value 2 Electronics temperature
Backlight
Switched off
Additional settings PIN
0000
Probe type
Like order
HART mode
Address 0 - Analogue current output
with HART
The instrument settings are copied with this function. The following
functions are available:
•
Read from sensor: Read data from sensor and store into the
display and adjustment module
•
Write into sensor: Store data from the display and adjustment
module back to the sensor
The following data or settings for adjustment of the display and ad-
justment module are saved:
•
All data of the menu "Setup" and "Display"
•
In the menu "Additional adjustments" the items "Reset, Date/Time"
•
Special parameters
Additional adjustments -
Copy instrument settings