VEGA VEGAFLEX 82 4 … 20 mA_HART four-wire User Manual
Page 32
32
6 Set up with the display and adjustment module
VEGAFLEX 82 • 4 … 20 mA/HART - four-wire
41830-EN-130314
You can choose between the following medium types:
Dielectric con-
stant
Medium type
Examples
> 3
Cereals, flour
All kind of cereals, wheat flour
1.5 … 3
Granules, cement Lime, gypsum, cement
< 1.5
Dusts, wood chips Wood chips, sawdust
In this menu item, you can enter the max. adjustment for the level.
Adjust the requested percentage value with [+] and save with [OK].
Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. The distance refers to the sensor
reference plane (seal surface of the process fitting). Keep in mind that
the max. level must lie below the dead band.
In this menu item, you can enter the min. adjustment for the level.
Adjust the requested percentage value with [+] and save with [OK].
Enter the suitable distance value in m for the empty vessel (e.g.
distance from the flange to the probe end) corresponding to the per-
centage value. The distance refers tot he sensor reference plane (seal
surface of the process fitting).
Setup - Max. adjustment
Level
Setup - Min. adjustment
Level