6 Set up with the display and adjustment module

VEGAFLEX 82 • 4 … 20 mA/HART - four-wire

41830-EN-130314

Since the HART variables are very extensive, the indication was

divided into two menu items.
In the menu "HART variables 1" you can have the first HART value PV

(primary value) and the second HART value SV (secondary value) of

the sensor displayed.
The values cannot be changed in the display and adjustment module.

To change these values, you have to use the adjustment software

PACTware.

In the menu "HART variables 2" you can have the third HART value

TV (third value) and the fourth HART value QV (quarter value) of the

sensor displayed.
The values cannot be changed in the display and adjustment module.

To change these values, you have to use the adjustment software

PACTware.

The following circumstances cause interfering reflections and can

influence the measurement:

High sockets

Vessel installations such as struts

Deflectors, etc.

Note:

A false signal suppression detects, marks and saves these false sig-

nals so that they are no longer taken into account for level measure-

ment.
This should be done with the lowest possible level so that all potential

interfering reflections can be detected.
Proceed as follows:

Enter the actual distance from the sensor to the product surface.

All interfering signals in this section are detected by the sensor and

stored.

Setup - HART variables

(1)

Setup - HART variables

(2)

Setup - False signal sup-

pression