Report unit number, Assign unit number, Set number of floats – VEGA VEGAFLEX 81 Modbus and Levelmaster protocol Coax probe User Manual
Page 81
81
11 Supplement
VEGAFLEX 81 • Modbus and Levelmaster protocol
42283-EN-130314
Response:
Parameter
Length
Code/Data
Report Level (and Temperature)
24 characters ASCII
UuuDlll.llFtttEeeeeWwwww
uu = Address
lll.ll = PV in inches
ttt = Temperature in Fahrenheit
eeee = Error number (0 no error, 1
level data not readable)
wwww = Warning number (0 no
warning)
Level in inches is repeated for sensors with 2 levels. PV value is transmitted as first measured value,
SV as second measured value.
PV, SV, TV and QV can be adjusted via the sensor DTM.
Report Unit Number
Request:
Parameter
Length
Code/Data
Report Unit Number
5 characters ASCII
U**N?
Response:
Parameter
Length
Code/Data
Report Level (and Temperature)
6 characters ASCII
UuuNnn
Assign Unit Number
Request:
Parameter
Length
Code/Data
Assign Unit Number
6 characters ASCII
UuuNnn
Response:
Parameter
Length
Code/Data
Assign Unit Number
6 characters ASCII
UuuNOK
uu = new Address
Set number of Floats
Request:
Parameter
Length
Code/Data
Set number of Floats
5 characters ASCII
UuuFn
Response:
Parameter
Length
Code/Data
Set number of Floats
6 characters ASCII
UuuFOK
If the number is set to 0, no level is returned