VEGA VEGAFLEX 81 Modbus and Levelmaster protocol Coax probe User Manual
Page 70
70
11 Supplement
VEGAFLEX 81 • Modbus and Levelmaster protocol
42283-EN-130314
Step response time
5)
≤ 3 s
Max. filling/emptying speed
1 m/min
Ambient conditions
Ambient, storage and transport tempera-
ture
-40 … +80 °C (-40 … +176 °F)
Process conditions
For the process conditions, please also note the specifications on the type label. The lowest value
always applies.
The measurement error from the process conditions is in the specified pressure and temperature
range of below 1 %.
Process pressure
Ʋ Standard version
-1 … +40 bar/-100 … +4000 kPa (-14.5 … +580 psig),
depending on the process fitting
Ʋ with borosilicate glass leadthrough
-1 … +100 bar/-100 … +10000 kPa
(-14.5 … +1450 psig), depending on the process fitting
Vessel pressure relating to the flange
nominal stage
see supplementary instructions manual "Flanges ac-
cording to DIN-EN-ASME-JIS"
Process temperature (thread or flange temperature)
Ʋ FKM (SHS FPM 70C3 GLT)
-40 … +150 °C (-40 … +302 °F)
Ʋ EPDM (A+P 75.5/KW75F)
-40 … +150 °C (-40 … +302 °F)
Ʋ FFKM (Kalrez 6375)
-20 … +150 °C (-4 … +302 °F)
Ʋ FFKM (Kalrez 6375)
-20 … +200 °C (-4 … +392 °F)
Ʋ with borosilicate glass leadthrough
-60 … +150 °C (-76 … +302 °F)
1
2
0°C
(32°F)
-40°C
(-104°F)
65°C
(149°F)
80°C
(176°F)
150°C
(302°F)
130°C
(266°F)
80°C
(176°F)
3
4
-40°C
(-104°F)
Fig. 34: Ambient temperature - process temperature, standard version
1 Ambient temperature
2 Process temperature (depending on the seal material)
3 Maximum permissible temperature - standard
4 Limited temperature range - plastic housing and stainless steel housing, electropolished
5)
Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk
solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2).