6 Set up with the display and adjustment module

VEGAFLEX 81 • Modbus and Levelmaster protocol

42283-EN-130314

In this menu item, you can select the application. You can choose

between level measurement and interface measurement. You can

also choose between measurement in a vessel or in a bypass or

standpipe.
Note:

The selection of the application has a considerable influence on all

other menu items. Keep in mind that as you continue with the param-

eter adjustment, individual menu items are only optionally available.
You have the possibility to choose the demonstration mode.This

mode is suitable for test and demonstration purposes. In this mode,

the sensor ignores the logic parameters of the application and reacts

immediately to each change.

In this menu item, you can define the medium type (product).
This menu item is only available if you have selected level measure-

ment under the menu item "Application".

You can choose between the following medium types:

Dielectric con-

stant

Medium type

Examples

> 10

Water-based liq-

uids

Acids, alcalis, water

3 … 10

Chemical mix-

tures

Chlorobenzene, nitro lacquer, aniline,

isocyanate, chloroform

< 3

Hydrocarbons

Solvents, oils, liquid gas

This menu item is only available, if you have chosen interface meas-

urement under the menu item "Application". In this menu item you can

enter if there is a superimposed gas phase in your application.
Only set the function to "Yes", if the gas phase is permanently pre-

sent.

Setup - Application - Ap-

plication

Setup - Application - Me-

dium, dielectric constant

Setup - Application - Gas

phase