9 Diagnostics and service

VEGAFLEX 81 • Modbus and Levelmaster protocol

42283-EN-130314

Fault description

Error pattern

Cause

Rectification

2. Measured value

jumps towards 100 %

Level

time

0

– Due to the process, the ampli-

tude of the product echo sinks

– A false signal suppression was

not carried out

– Carry out false signal suppres-

sion

– Amplitude or position of a

false signal has changed (e.g.

buildup); false signal suppres-

sion no longer matches

– Determine the reason for the

changed false signals, carry out

false signal suppression, e.g.

with buildup

Measurement error during filling

Fault description

Error pattern

Cause

Rectification

3. Measured value re-

mains in the area of the

bottom during filling

Level

time

0

– Echo from the probe end larger

than the product echo, for

example, with products with

ε

r

< 2.5 oil-based, solvents, etc.

– Check application parameter

"Medium" and "Vessel height",

adapt if necessary

4. Measured value re-

mains momentarily

unchanged during fill-

ing and then jumps to

the correct level

Level

time

0

– Turbulence on the product

surface, quick filling

– Check application parameters,

change if necessary, e.g. in

dosing vessel, reactor

5. Measured value

jumps sporadically to

100 % during filling

Level

time

0

– Varying condensation or con-

tamination on the probe

– Carry out false signal suppres-

sion

6. Measured value

jumps to ≥ 100 % or

0 m distance

Leve

l

time

0

– Level echo is no longer

detected in the close range

due to false signals in the close

range. The sensor goes into

overfill protection mode. The

max. level (0 m distance) as

well as the status message

"Overfill protection" are output-

ted.

– Eliminate false signals in the

close range

– Check installation conditions

– If possible, switch off the func-

tion "Overfill protection"

Measurement error during emptying

Fault description

Error pattern

Cause

Rectification

7. Measured value re-

mains unchanged in

the close range during

emptying

Level

time

0

– False echo larger than the level

echo

– Level echo too small

– Eliminate false signals in the

close range

– Remove contamination on the

probe. After having removed

the source of the false signals,

the false signal suppression

must be deleted.

– Carry out a new false signal

suppression

8. Measured value re-

mains reproducible

in one position during

emptying

Level

time

0

– Stored false signals in this

position are larger than the

level echo

– Delete false signal memory

– Carry out a new false signal

suppression