beautypg.com

VEGA VEGAFLEX 81 Modbus and Levelmaster protocol Coax probe User Manual

Page 30

background image

30

6 Set up with the display and adjustment module

VEGAFLEX 81 • Modbus and Levelmaster protocol

42283-EN-130314

This menu item is only available if you have selected interface meas-

urement under the menu item "Application". In this menu item you can

choose the medium type of the upper medium.

You can enter the dielectric figure of the upper medium directly or

have the figure determined by the instrument. For this purpose you

have to enter the measured distance to the interface.

In this menu item you can enter the max. adjustment for the level. With

interface measurement this is the maximum total level.

Adjust the requested percentage value with [+] and save with [OK].

Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. The distance refers to the sensor

reference plane (seal surface of the process fitting). Keep in mind that

the max. level must lie below the dead band.

In this menu item you can enter the min. adjustment for the level. With

interface measurement this is the minimum total level.

Adjust the requested percentage value with [+] and save with [OK].

Enter the suitable distance value in m for the empty vessel (e.g.

distance from the flange to the probe end) corresponding to the per-

Setup - Application - Di-

electric constant

Setup - Max. adjustment

Level

Setup - Min. adjustment

Level