6 Set up with the display and adjustment module

VEGAFLEX 81 • Modbus and Levelmaster protocol

42283-EN-130314

In the menu item "Lock/unlock adjustment", you can protect the

sensor parameters against unauthorized modification. The PIN is

activated/deactivated permanently.
The following adjustment functions are possible without entering the

PIN:

Select menu items and show data

Read data from the sensor into the display and adjustment mod-

ule.

Caution:

With active PIN, adjustment via PACTware/DTM as well as other

systems is also blocked.
You can change the PIN number under "Additional adjustments -

PIN".

This menu item enables the setting of the requested national lan-

guage.

In the delivery status, the sensor is set to the ordered national lan-

guage.

In this menu item, you define the indication of the measured value

on the display. You can display two different measured values. In this

menu item, you define measured value 1.

The default setting for the displayed value 1 is "Filling height Level".

In this menu item, you define the indication of the measured value

on the display. You can display two different measured values. In this

menu item, you define measured value 2.

The default setting for the displayed value 2 is the electronics tem-

perature.

Lock/unlock setup - Ad-

justment

Display - Menu language

Display - Displayed value

1

Display - Displayed value

2