VEGA VEGAFLEX 86 Foundation Fieldbus User Manual
Page 84
84
11 Supplement
VEGAFLEX 86 • Foundation Fieldbus
44233-EN-130910
Gas phase
Temperature
Pressure
10 bar
(145 psig)
50 bar
(725 psig)
100 bar
(1450 psig)
200 bar
(2900 psig)
400 bar
(5800 psig)
Steam (satu-
rated steam)
100 °C/212 °F -
-
-
-
-
180 °C/356 °F 2.1 %
-
-
-
-
264 °C/507 °F 1.44 %
9.2 %
-
-
-
366 °C/691 °F 1.01 %
5.7 %
13.2 %
76.0 %
-
Characteristics and performance data
Measuring cycle time
< 500 ms
Step response time
4)
≤ 3 s
Max. filling/emptying speed
1 m/min
Ambient conditions
Ambient, storage and transport tempera-
ture
-40 … +80 °C (-40 … +176 °F)
Process conditions
For the process conditions, please also note the specifications on the type label. The lowest value
always applies.
The measurement error from the process conditions is in the specified pressure and temperature
range of below 1 %.
Vessel pressure relating to the flange
nominal stage
see supplementary instructions manual "Flanges ac-
cording to DIN-EN-ASME-JIS"
Process pressure
-1 … +400 bar/-100 … +40000 kPa
(-14.5 … +5800 psig), depending on the process fitting
Process temperature
-196 … +280 °C (-321 … +536 °F)
1
2
0°C
(32°F)
-40°C
(-104°F)
65°C
(149°F)
80°C
(176°F)
280°C
(536°F)
250°C
(482°F)
190°C
(374°F)
3
4
-196°C
(-321°F)
-80°C
(-112°F)
55°C
(131°F)
Fig. 62: Ambient temperature - process temperature (version -196 … +280 °C/-321 … +536 °F)
1 Ambient temperature
2 Process temperature (depending on the seal material)
3 Maximum permissible temperature - standard
4 Limited temperature range - plastic housing and stainless steel housing, electropolished
4)
Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk
solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2).