3 Product description

VEGAFLEX 86 • Foundation Fieldbus

44233-EN-130910

This operating instructions manual applies to the following instrument

versions:

Hardware from 1.0.0

Software from 1.0.0

Only for instrument versions without SIL qualification

This electronics version can be determined via the product code on

the type label as well as on the electronics.

Standard electronics: Type FX80FF.-

The scope of delivery encompasses:

Sensor

Documentation

– this operating instructions manual

– Test certificate measuring accuracy (optional)

– Operating instructions manual "Display and adjustment mod-

ule" (optional)

– Supplementary instructions "GSM/GPRS radio module"

(optional)

– Supplementary instructions manual "Heating for display and

adjustment module" (optional)

– Supplementary instructions manual "Plug connector for con-

tinuously measuring sensors" (optional)

– Ex-specific "Safety instructions" (with Ex versions)

– if necessary, further certificates

3.2 Principle of operation

The VEGAFLEX 86 is a level sensor with cable or rod probe for

continuous level or interface measurement, particularly suitable for

applications in high temperatures up to +450 °C (842 °F).

High frequency microwave pulses are guided along a steel cable or

a rod. Upon reaching the product surface, the microwave pulses are

reflected. The running time is evaluated by the instrument and output-

ted as level.

Scope of this operating

instructions manual

Versions

Scope of delivery

Application area

Functional principle -

level measurement