beautypg.com

6 exchange or shorten cable/rod – VEGA VEGAFLEX 86 Foundation Fieldbus User Manual

Page 72

background image

72

9 Diagnostics and service

VEGAFLEX 86 • Foundation Fieldbus

44233-EN-130910

Or on site by the user

In both cases, the serial number of the sensor is needed. The serial

numbers are stated on the type label of the instrument, on the inside

of the housing as well as on the delivery note.
When loading on site, first of all the order data must be downloaded

from the Internet (see operating instructions manual "Electronics

module").

9.6 Exchange or shorten cable/rod

The cable or rod (meas. part) of the probe can be shortened, if neces-

sary. To loosen the rod or cable you need a fork spanner with spanner

width 13.
1. Loosen the rod or cable by applying a fork spanner to the flat

surfaces (SW 13), provide counterforce with another fork spanner

(SW 13)

2. Unscrew the loosened rod or cable manually.
3. Place the enclosed new double washer onto the thread.
Caution:

Make sure that the two components of the double washer remain

together.
4. Screw the new rod and the new cable manually to the thread on

the process fitting.

5. Exert counterforce with the second fork spanner and tighten the

or or cable on the flat surfaces with a torque of 20 Nm (15 lbf ft).

Exchanging the cable/rod