beautypg.com

VEGA VEGAFLEX 86 Foundation Fieldbus User Manual

Page 23

background image

23

4 Mounting

VEGAFLEX 86 • Foundation Fieldbus

44233-EN-130910

1

2

Fig. 13: Mounting the instrument on insulated vessels.
1 Temperature insulation

2 Ambient temperature on the housing

If there is a risk of the cable probe touching the vessel wall during

operation due to product movements or agitators, etc., the measuring

probe should be securely fixed.
In the gravity weight there is an internal thread (M8), e.g. for an eye-

bolt (optional) - (article no. 2.1512).
Make sure that the probe cable is not completely taut. Avoid tensile

loads on the cable.
Avoid undefined vessel connections, i.e. the connection must be

either grounded reliably or isolated reliably. Any undefined change of

this requirement can lead to measurement errors.

Fasten