beautypg.com

Thermo electron autopilot – VEGA VEGABAR 87 Modbus and Levelmaster protocol - Operating Instructions User Manual

Page 74

background image

74

10 Supplement

VEGABAR 87 • Modbus and Levelmaster protocol

46297-EN-131107

Thermo Electron Autopilot

Wiring plan

+

+

power supply

MODBU

S

D0

D1

IS GND

US

B

1

2

3

13

45

2o

ff

on

(

)

(

)

(-)

(-)

+8

+30 Vdc

to

GND

2

1

Rx -

Rx+

Fig. 32: Connection of VEGABAR 87 to RTU Thermo Electron Autopilot
1 VEGABAR 87

2 RTU Thermo Electron Autopilot

3 Voltage supply

Parameter

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

IEE Fit 2R

Input Register Base Number

0

The basic number of the input registers is always added to the input register address of VEGABAR

87.
Address 1300 must hence be entered as register address for 1300 for RTU Thermo Electron Auto-

pilot.