4 modbus rtu commands, Fc3 read holding register, Fc4 read input register – VEGA VEGABAR 87 Modbus and Levelmaster protocol - Operating Instructions User Manual
Page 65
65
10 Supplement
VEGABAR 87 • Modbus and Levelmaster protocol
46297-EN-131107
Unit Code
Measurement Unit
47
Inches
48
Centimeters
49
Millimeters
111
Cubic Yards
112
Cubic Feet
113
Cubic Inches
10.4 Modbus RTU commands
FC3 Read Holding Register
With this command, any number (1-127) of holding registers can be read out. The start register,
from which the readout should start, and the number of registers are transmitted.
Request:
Parameter
Length
Code/Data
Function Code
1 Byte
0x03
Start Address
2 Bytes
0x0000 to 0xFFFF
Number of Registers
2 Bytes
1 to 127 (0x7D)
Response:
Parameter
Length
Code/Data
Function Code
1 Byte
0x03
Start Address
2 Bytes
2*N
Register Value
N*2 Bytes
Data
FC4 Read Input Register
With this command, any number (1-127) of input registers can be read out. The start register, from
which the readout should start, and the number of registers are transmitted.
Request:
Parameter
Length
Code/Data
Function Code
1 Byte
0x04
Start Address
2 Bytes
0x0000 to 0xFFFF
Number of Registers
N*2 Bytes
1 to 127 (0x7D)
Response:
Parameter
Length
Code/Data
Function Code
1 Byte
0x04
Start Address
2 Bytes
2*N
Register Value
N*2 Bytes
Data