6 Set up with the display and adjustment module
VEGABAR 87 • Modbus and Levelmaster protocol
46297-EN-131107
6. Min. adjustment
In this menu item you carry out the min. adjustment for level
Enter the percentage value and the corresponding value for the min.
level.
The quick setup is hence finished.
6.4 Parameter adjustment - Extended adjustment
For technically demanding measurement loops you can carry out
extended settings in "Extended adjustment".
The main menu is divided into five sections with the following func-
tions:
Setup: Settings, e.g., for measurement loop name, application, units,
position correction, adjustment, signal output
Display: Settings, e.g., for language, measured value display, lighting
Diagnosis: Information, e.g. on instrument status, pointer, measure-
ment reliability, simulation
Additional adjustments: PIN, units SV 2, date/time, reset, copy
function
Info: Instrument name, hardware and software version, date of manu-
facture, device ID, sensor features
In the main menu point "Setup", the individual submenu points should
be selected subsequently and provided with the correct parameters
to ensure the optimum adjustment of the measurement. The menu
items are described in the following.
In the menu item "Sensor TAG" you edit a twelve digit measurement
loop designation label.
You can enter an unambiguous designation for the sensor, e.g. the
measurement loop name or the tank or product designation. In digital
systems and in the documentation of larger plants, a singular desig-
nation must be entered for exact identification of individual measuring
points.
The available digits comprise:
•
Letters from A … Z
•
Numbers from 0 … 9
Main menu
Setup - Measurement
loop name