Report level (and temperature), Report unit number, Assign unit number – VEGA VEGABAR 87 Modbus and Levelmaster protocol - Operating Instructions User Manual
Page 69
69
10 Supplement
VEGABAR 87 • Modbus and Levelmaster protocol
46297-EN-131107
Report Level (and Temperature)
Request:
Parameter
Length
Code/Data
Report Level (and Temperature)
4 characters ASCII
Uuu?
Response:
Parameter
Length
Code/Data
Report Level (and Temperature)
24 characters ASCII
UuuDlll.llFtttEeeeeWwwww
uu = Address
lll.ll = PV in inches
ttt = Temperature in Fahrenheit
eeee = Error number (0 no error, 1
level data not readable)
wwww = Warning number (0 no
warning)
Level in inches is repeated for sensors with 2 levels. PV value is transmitted as first measured value,
SV as second measured value.
PV, SV, TV and QV can be adjusted via the sensor DTM.
Report Unit Number
Request:
Parameter
Length
Code/Data
Report Unit Number
5 characters ASCII
U**N?
Response:
Parameter
Length
Code/Data
Report Level (and Temperature)
6 characters ASCII
UuuNnn
Assign Unit Number
Request:
Parameter
Length
Code/Data
Assign Unit Number
6 characters ASCII
UuuNnn
Response:
Parameter
Length
Code/Data
Assign Unit Number
6 characters ASCII
UuuNOK
uu = new Address