beautypg.com

Report number of floats, Report receive to transmit delay, Error codes – VEGA VEGABAR 87 Modbus and Levelmaster protocol - Operating Instructions User Manual

Page 71

background image

71

10 Supplement

VEGABAR 87 • Modbus and Levelmaster protocol

46297-EN-131107

Report Number of Floats

Request:

Parameter

Length

Code/Data

Set Receive to Transmit Delay

4 characters ASCII

UuuF

Response:

Parameter

Length

Code/Data

Set Receive to Transmit Delay

5 characters ASCII

UuuFn
n = number of measurement values

(0, 1 or 2)

Report Receive to Transmit Delay

Request:

Parameter

Length

Code/Data

Report Receive to Transmit Delay

4 characters ASCII

UuuR

Response:

Parameter

Length

Code/Data

Report Receive to Transmit Delay

7 characters ASCII

UuuRmmm
mmm = milliseconds (50 up to 250),

default = 127 ms

Error codes

Error Code

Name

EE-Error

Error While Storing Data in EEPROM

FR-Error

Erorr in Frame (too short, too long, wrong data)

LV-Error

Value out of limits