beautypg.com

6 configuration of typical modbus hosts, Fisher roc 809 – VEGA VEGABAR 87 Modbus and Levelmaster protocol - Operating Instructions User Manual

Page 72

background image

72

10 Supplement

VEGABAR 87 • Modbus and Levelmaster protocol

46297-EN-131107

10.6 Configuration of typical Modbus hosts

Fisher ROC 809

Wiring plan

+

+

power supply

MODBU

S

D0

D1

IS GND

US

B

B

COM

Z

Y

A

(Rx/Tx -)

(Rx/Tx +)

1

2

3

13

45

2o

ff

on

(

)

(

)

(-)

(-)

+8

+30 Vdc

to

GND

Fig. 30: Connection of VEGABAR 87 to RTU Fisher ROC 809
1 VEGABAR 87

2 RTU Fisher ROC 809

3 Voltage supply

Parameter

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

Conversion Code 66

Input Register Base Number

0

The basic number of the input registers is always added to the input register address of VEGABAR

87.
Address 1300 must hence be entered as register address for RTU Fisher ROC 809.