Input register – VEGA VEGABAR 87 Modbus and Levelmaster protocol - Operating Instructions User Manual
Page 63
63
10 Supplement
VEGABAR 87 • Modbus and Levelmaster protocol
46297-EN-131107
Register Name Register Num-
ber
Type
Configurable
Values
Default Value
Unit
Baud Rate
201
Word
1200, 2400,
4800, 9600,
19200
9600
-
Parity
202
Word
0 = None, 1 =
Odd, 2 = Even
0
-
Stopbits
203
Word
1 = None, 2 =
Two
1
-
Delay Time
206
Word
10 … 250
50
ms
Byte Oder (Float-
ing point format)
3000
Word
0, 1, 2, 3
0
-
Input register
The input registers consist of 16 bits. They can only be read out. Before each command, the ad-
dress (1 byte) is sent, after each command a CRC (2 bytes) is sent.
PV, SV, TV and QV can be adjusted via the sensor DTM.
Register Name
Register Number
Type
Note
Status
100
DWord
Bit 0: Invalid Measurement Value PV
Bit 1: Invalid Measurement Value SV
Bit 2: Invalid Measurement Value TV
Bit 3: Invalid Measurement Value QV
PV Unit
104
DWord
Unit Code
PV
106
Primary Variable in Byte Order CDAB
SV Unit
108
DWord
Unit Code
SV
110
Secondary Variable in Byte Order CDAB
TV Unit
112
DWord
Unit Code
TV
114
Third Variable in Byte Order CDAB
QV Unit
116
DWord
Unit Code
QV
118
Quarternary Variable in Byte Order CDAB
Status
1300
DWord
See Register 100
PV
1302
Primary Variable in Byte Order of Register 3000
SV
1304
Secondary Variable in Byte Order of Register 3000
TV
1306
Third Variable in Byte Order of Register 3000
QV
1308
Quarternary Variable in Byte Order of Register 3000
Status
1400
DWord
See Register 100
PV
1402
Primary Variable in Byte Order CDAB
Status
1412
DWord
See Register 100
SV
1414
Secondary Variable in Byte Order CDAB