10 Supplement

VEGABAR 87 • Modbus and Levelmaster protocol

46297-EN-131107

Register Name Register Num-

ber

Type

Configurable

Values

Default Value

Unit

Baud Rate

201

Word

1200, 2400,

4800, 9600,

19200

9600

-

Parity

202

Word

0 = None, 1 =

Odd, 2 = Even

0

-

Stopbits

203

Word

1 = None, 2 =

Two

1

-

Delay Time

206

Word

10 … 250

50

ms

Byte Oder (Float-

ing point format)

3000

Word

0, 1, 2, 3

0

-

Input register

The input registers consist of 16 bits. They can only be read out. Before each command, the ad-

dress (1 byte) is sent, after each command a CRC (2 bytes) is sent.
PV, SV, TV and QV can be adjusted via the sensor DTM.

Register Name

Register Number

Type

Note

Status

100

DWord

Bit 0: Invalid Measurement Value PV
Bit 1: Invalid Measurement Value SV
Bit 2: Invalid Measurement Value TV
Bit 3: Invalid Measurement Value QV

PV Unit

104

DWord

Unit Code

PV

106

Primary Variable in Byte Order CDAB

SV Unit

108

DWord

Unit Code

SV

110

Secondary Variable in Byte Order CDAB

TV Unit

112

DWord

Unit Code

TV

114

Third Variable in Byte Order CDAB

QV Unit

116

DWord

Unit Code

QV

118

Quarternary Variable in Byte Order CDAB

Status

1300

DWord

See Register 100

PV

1302

Primary Variable in Byte Order of Register 3000

SV

1304

Secondary Variable in Byte Order of Register 3000

TV

1306

Third Variable in Byte Order of Register 3000

QV

1308

Quarternary Variable in Byte Order of Register 3000

Status

1400

DWord

See Register 100

PV

1402

Primary Variable in Byte Order CDAB

Status

1412

DWord

See Register 100

SV

1414

Secondary Variable in Byte Order CDAB