8 saving the parameter adjustment data – VEGA MINITRAC 31 Foundation Fieldbus User Manual
Page 58
58
6 Set up with the display and adjustment module
MINITRAC 31 • Foundation Fieldbus
41782-EN-131119
Enter here, the respective application.
This menu item enables adaptation of the sensor to the requested ap-
plication. You can choose between the following applications: "Level",
"Density", "Limit level", "X-ray alarm" or "Real value correction".
With this menu item you safeguard the sensor parameters against
unauthorized or unintentional modifications.
This menu item is described in the operating instructions manual
"Display and adjustment module".
6.8 Saving the parameter adjustment data
We recommended noting the adjusted data, e.g. in this operating
instructions manual, and archiving them afterwards. They are thus
available for multiple use or service purposes.
If the instrument is equipped with a display and adjustment module,
the data in the sensor can be saved in the display and adjustment
module. The procedure is described in the operating instructions
manual "Display and adjustment module" in the menu item "Copy
sensor data". The data remain there permanently even if the sensor
power supply fails.
The following data or settings for adjustment of the display and ad-
justment module are saved:
•
All data of the menu "Setup" and "Display"
•
In the menu "Additional adjustments" the items "Sensor-specific
units, temperature unit and linearization"
•
The values of the user programmable linearization curve
The function can also be used to transfer settings from one instru-
ment to another instrument of the same type. If it is necessary to
exchange a sensor, the display and adjustment module is inserted
into the replacement instrument and the data are likewise written into
the sensor via the menu item "Copy sensor data".
Setup - Application
Lock setup - adjustment